F109-46

Voltage supply of encoder faulty (A3403 = encoder 1 and A3404 = encoder 2)

SEW Eurodrive · MOVIDRIVE MDX60B/61B Variable Speed Drive

What does F109-46 mean?

The encoder voltage supply (A3403 or A3404) is outside the defined range (min. DC 20 V / max. DC 29 V). This can be caused by an overload in the supply voltage, potentially tripping an internal polyswitch fuse on the DCS..B option.

Source: SEW Eurodrive MOVIDRIVE MDX60B/61B Variable Speed Drive
Open Manual (Page 214)