Incorrect motor/inverter assignment
SEW Eurodrive · Drives
What does 90 mean?
A mismatch has been detected between the assigned motor type and the MOVIMOT inverter. This indicates that the connected motor is incompatible with the inverter's configuration or capabilities.
Common Causes
- Incompatible motor connected to the MOVIMOT inverter
- Incorrect motor type selection or parameterization in the drive settings
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the installed motor's nameplate data (e.g., model, power, voltage, current) against the MOVIMOT inverter's specified motor compatibility list and the intended motor assignment.
- 2
Check and confirm all motor-specific parameters (e.g., nominal voltage, current, frequency, RPM, motor type selection) configured within the MOVIMOT inverter's software or HMI against the connected motor's nameplate.
- 3
Inspect the physical wiring connections between the MOVIMOT inverter and the motor for correct phase assignment, secure termination, and any signs of damage or loose contacts that could affect motor identification.
- 4
Verify the MOVIMOT inverter's model number and firmware version are appropriate for the connected motor type and application, referencing official SEW Eurodrive documentation.