Current Limit Exceeded
SEW Eurodrive · [PDF] MOVIMOT® MM..D with AC Motor DT/DV / Operating Instruc
What does 44 mean?
This error is generated if the drive operates at its adjustable current limit for longer than 500 ms, occurring when additional function 2 (adjustable current limitation) is active and the operating frequency is above 15 Hz. Prolonged operation at current limit can indicate an overloaded condition.
Common Causes
- Drive operating at the current limit for longer than 500 ms.
- Adjustable current limit set too low via DIP switch f2 (Imax [%] of IN).
- Excessive load on the drive when the monitoring function is active (above 15 Hz).
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check the mechanical load on the drive and reduce it if necessary.
- 2
Review the setting of DIP switch f2 for the adjustable current limit (Imax [%] of IN) and increase it if appropriate for the application.
- 3
Verify the operating frequency is above 15 Hz, as this monitoring function is active only then.
- 4
Reset the fault by switching off and then switching on the DC 24V supply voltage.
- 5
Reset the error via the error reset function.