F72
External AC Contactor Malfunction
Schneider Electric · XW Pro NA Operation Guide
What does F72 mean?
This Manual Fault occurs when the External AC Contactor or a latching relay within the Battery Control System (BCS) is not in its expected commanded state. This signifies a failure in the external AC power path control, impacting power flow.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
For Contactor: Check for fusing of coil, damaged or broken wiring and connections, and damaged inverter aux port.
- 4
For BCS: Check for broken (welded) contactor/relay, damaged or broken wiring and connections, and damaged inverter aux port.
Source: Schneider Electric XW Pro NA Operation Guide