F57
FET1 Over Temperature Shutdown
Schneider Electric · XW Pro NA Operation Guide
What does F57 mean?
This Automatic Fault occurs when the internal temperature of FET1 exceeds 105 °C, triggering a shutdown to protect the inverter's power components. The fault clears automatically when the temperature drops to 75 °C.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Let inverter cool down and try restarting if ambient temperature is high.
- 4
Hold a piece of paper to inverter vents to check the fan; if failed, have inverter serviced.
- 5
Increase clearance around the inverter or unclog the fan air intake.
Source: Schneider Electric XW Pro NA Operation Guide
View Official PDF