FCF2
Output Contactor Open
Schneider Electric · Altivar Machine ATV320 Variable Speed Drive
What does FCF2 mean?
Indicates that the output contactor is detected as open when it should be closed. This prevents the drive from supplying power to the motor, resulting in a failure to start or operate. This could be due to a wiring issue, contactor fault, or an active interlock.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Ensure all safety interlocks or permissive conditions for contactor closure are met.
- 4
Measure the voltage supplied to the contactor coil when it should be energized.
Source: Schneider Electric Altivar Machine ATV320 Variable Speed Drive
View Official PDF