OLF
Motor Overload
Schneider Electric · Altivar 312 Variable Frequency Drive
What does OLF mean?
This fault indicates that the motor is drawing excessive current, exceeding its thermal protection limits. This can be caused by a mechanical overload on the motor or incorrect configuration of the motor's thermal current parameter (ItH) or stator resistance (rSC). Prolonged operation under overload can lead to motor winding damage or premature failure.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Wait for the drive and motor to cool down before attempting to restart.
- 4
Remeasure the cold stator resistance and update the [Cold stator resist.] (rSC) parameter (page 42).
Source: Schneider Electric Altivar 312 Variable Frequency Drive
View Official PDF