PHF

Loss of a Line Phase

Schneider Electric · Altistart 22 Soft Starter

What does PHF mean?

One or more incoming line phases to the soft starter are either completely missing or have significantly reduced voltage. This leads to single-phasing conditions which are highly destructive to three-phase motors and can damage the soft starter.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Check the motor connections and any isolating devices between the soft starter and motor for integrity.

  2. 4

    Assess the general state of the motor for any pre-existing damage or signs of single-phasing.

  3. 5

    Verify the line frequency is within tolerance and check the configuration of the 'PHL' parameter (Phase Loss detection) in the 'PrO' menu if applicable.

Source: Schneider Electric Altistart 22 Soft Starter