bLF

BRAKE CONTROL FAULT

Schindler · Altivar 312 Drive

What does bLF mean?

This fault indicates an issue with the brake control system, where the brake release current may not have been reached or the brake engage frequency threshold ([Brake engage freq] (bEn)) is incorrectly set or not assigned despite brake control ([Brake assignment] (bLC)) being active. This can lead to improper motor braking or starting.

Common Causes

  • Brake release current not reached
  • Brake engage frequency threshold ([Brake engage freq] (bEn)) = [No] (not set) whereas the brake control ([Brake assignment] (bLC)) is assigned

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the drive/motor connection.

  2. 2

    Check the motor windings.

  3. 3

    Check the [Brake release I FW] (Ibr) setting in the [APPLICATION FUNCT.] (FUn-) menu, page 85.

  4. 4

    Apply the recommended settings for [Brake engage freq] (bEn), pages 84 and 85.