OCA

Short Circuit Inverter at Start

Schindler · Altivar 212 Variable Frequency Drive

What does OCA mean?

This fault indicates a short circuit condition detected within the Altivar 212 drive's output inverter stage during motor startup, usually caused by a ground fault.

Common Causes

  • Ground fault in the inverter output or motor/cables.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Use a 1000 V testing tool (megger) to check the motor windings for insulation resistance to ground.

  2. 2

    Use a 1000 V testing tool (megger) to check the motor cables for insulation resistance to ground.