E03.
Overcurrent Protection During Acceleration
Omron · MX2 Series Type V2 Compact Inverter
What does E03. mean?
An overcurrent trip during motor acceleration signifies an excessive current draw, often caused by rapid acceleration times, a locked rotor condition, or improperly tuned torque boost parameters. The inverter detects this condition when output current reaches approximately 200% of its rated value, leading to a shutdown to protect the main power elements.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If torque boost is enabled, decrease the torque boost setting (A041/A241, A042/A242) to an appropriate level.
- 4
For PM motors, ensure motor parameters (H003/H203, H004/H204, H105, H123) are correctly set and adjusted according to the motor specifications.
Source: Omron MX2 Series Type V2 Compact Inverter