E80

Encoder Disconnection

Omron · MX2 Inverter

What does E80 mean?

This fault indicates that the encoder connected for feedback has been disconnected, has a wiring error, or is of an unsupported type (e.g., not line driver output). Without valid encoder feedback, the inverter cannot perform accurate speed or position control, leading to a shutdown to prevent erratic motor behavior.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Confirm that the encoder type (e.g., line driver output, pulse count) is compatible with the inverter's specifications and settings.

  2. 4

    Review and correctly set encoder parameters (P003, P004, P011) in the inverter to match the installed encoder.

  3. 5

    If all connections and settings are correct, the encoder itself may be faulty and require replacement.

Source: Omron MX2 Inverter