035

Starting Frequency Exceeds Multi-step Speed Reference 0

Omron · MX2 Inverter

What does 035 mean?

This warning indicates that the inverter's starting frequency (b082) is set higher than the Multi-step speed reference 0 (A020) or the output frequency setting (F001). This creates a logical conflict for initial motor speed settings, potentially causing the drive to jump to a higher speed than intended immediately after starting.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Increase A020 (Multi-step speed reference 0) to accommodate the desired starting frequency if this is the intended operation.

Source: Omron MX2 Inverter