Function Incompatible with Control Mode
Yaskawa · V1000
Hva betyr oPE08 ?
A parameter or function has been configured that is not supported or compatible with the currently selected control mode of the drive. This error often arises after a control mode change, requiring a thorough review of parameter settings to match the new mode of operation.
Vanlige årsaker
- Drive control method (Parameter A1-02, e.g., V/f, Sensorless Vector, Closed Loop Vector) was changed, and a previously configured parameter is incompatible with the new mode.
- Attempting to use advanced motor control functions (e.g., flux vector tuning, auto-tuning) while the drive is set to a basic V/f control mode.
- PID function (e.g., b3-01) is enabled or configured, but the selected control mode (A1-02) does not support integrated PID.
- Specific output functions (e.g., pulse output, specific relay functions) are not available in the currently selected control mode.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Identify the currently selected drive control method by checking Parameter A1-02.
- 2
2. Determine which specific parameter or function (often indicated by the fault message or recent changes) is causing the incompatibility.
- 3
3. Refer to the drive's programming manual to verify which parameters and functions are compatible with the control mode set in A1-02.
- 4
4. Either change the incompatible parameter/function to a compatible setting or adjust Parameter A1-02 to a control mode that supports the desired function.
- 5
5. Perform a parameter initialization (Parameter A1-03) to reset all parameters to default for the current control mode, then reconfigure from scratch if necessary.
- 6
6. Perform a drive power cycle after setting the parameters.