Ground Fault

Ground Fault

Yaskawa · V1000

Hva betyr Ground Fault ?

The ground leakage current on the drive's output side has surpassed 50% of the drive's rated output current. This often indicates damaged motor or cable insulation, or excessive stray capacitance due to long cable runs. This condition poses a serious electrical safety hazard and potential damage to the motor or drive.

Vanlige årsaker

  • Damaged insulation on the motor output cables (U, V, W) to ground, potentially due to mechanical abrasion, crushing, or chemical exposure.
  • Internal insulation breakdown within the motor windings (U, V, W phases) to the motor frame (ground) due to overheating or aging.
  • Water ingress or excessive moisture in the motor or terminal box, reducing insulation resistance to ground.
  • Excessive cable length between the drive and motor, leading to high stray capacitance to ground, especially with unshielded cables.
  • Incorrectly terminated or damaged motor cable shield, allowing leakage currents to flow to ground.
  • Drive's ground fault detection sensitivity (e.g., Parameter L2-03) is set too high for the application, especially with multiple motors or long cables.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Power down the drive completely (wait for DC bus discharge). Disconnect all motor leads (U, V, W) from the drive's output terminals.

  2. 2

    2. Perform an insulation resistance test (Megger test at 500-1000VDC) on each motor phase (U, V, W) to the motor frame ground. Reading should be >1MΩ, ideally >100MΩ.

  3. 3

    3. Inspect the entire length of the motor cable for any visible damage to the outer jacket or signs of wear that could compromise insulation.

  4. 4

    4. Measure the insulation resistance of the motor cable from each conductor (U, V, W) to the cable shield/ground.

  5. 5

    5. Verify the motor cable shield is correctly terminated and grounded at both the drive and motor ends. Ensure no stray strands are touching ground.

  6. 6

    6. If the ground fault detection parameter (e.g., L2-03 'Ground Fault Detection Level') is adjustable, slightly reduce its sensitivity if the cable length is excessively long (over 50m) and insulation is verified good.

Se alle koder i denne manualen (87)
Verifisert teknisk data. Sist oppdatert: March 2026