Control Power Supply Undervoltage
Yaskawa · P1000
Hva betyr Uv2 ?
The drive detected an undervoltage condition specifically in the control power supply circuit. This affects the internal logic and control functions of the drive.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the main input voltage (L1-L2, L2-L3, L3-L1) at the drive's R/L1, S/L2, T/L3 terminals and verify against the nominal supply voltage.
- 2
Inspect all main power input wiring connections at the drive terminals and upstream power distribution for looseness, corrosion, or signs of damage.
- 3
Verify drive parameters related to input voltage settings and undervoltage trip levels (e.g., L1-01, L2-01) match the actual system supply and electrical drawings.
- 4
If the drive utilizes a separate auxiliary control power input (e.g., 24VDC or 110VAC control source), measure its voltage at the dedicated terminals and confirm it is within specified operating limits.