rH

Braking Resistor Overheat

Yaskawa · P1000

Hva betyr rH ?

The external braking resistor connected to the drive has overheated. This indicates excessive energy dissipation, potentially due to frequent or heavy braking, or inadequate resistor sizing/cooling.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the external braking resistor for physical damage, discoloration, and proper mounting.

  2. 2

    Verify all wiring connections to the braking resistor and the drive's braking terminals (B1, B2) are secure and free of corrosion.

  3. 3

    Measure the actual resistance of the braking resistor and compare it against the specified value and power rating (Ohms and Watts) as per system design or Yaskawa documentation.

  4. 4

    Check for adequate airflow and cooling around the braking resistor; remove any obstructions or debris impeding heat dissipation.

  5. 5

    Verify drive parameters related to deceleration time (e.g., C1-03, C1-04) and braking resistor usage (e.g., L3-01 to L3-08) are correctly configured for the application and match the system design.