Low Feedback/Water Fault
Yaskawa · iQpump Simplex Pump Drive
Hva betyr LFB/LW ?
The iQpump has detected that the feedback signal level has fallen below the programmed threshold (P1-07) and remained below this level for the duration specified in parameter P1-08. This condition triggers a fault, causing the iQpump to coast to a stop for system protection. This fault function is only active during running in auto mode.
Vanlige årsaker
- Feedback signal level falling below the P1-07 (Low Feedback Level) threshold.
- Sustained low feedback level for a period exceeding P1-08 (Low Feedback Level Fault Delay Time).
- Actual low water level or insufficient process variable in the system.
- A faulty feedback transducer providing a continuously low or zero signal.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify parameter P1-07 (Low Feedback Level) is set to the correct minimum allowable feedback value for the system.
- 2
Verify parameter P1-08 (Low Feedback Level Fault Delay Time) is set appropriately to detect sustained issues without nuisance tripping.
- 3
Measure the actual process variable (e.g., water level, pressure) and compare it to the feedback signal reported by the iQpump.
- 4
Check the feedback transducer for proper operation and inspect its wiring and connections for integrity.