Oversetter...
OL1

Motor Thermal Overload Fault

Yaskawa · F7 Drive

Hva betyr OL1 ?

The OL1 fault is triggered when the motor connected to the drive experiences prolonged overcurrent, causing it to exceed its thermal capacity. This protection is configured by parameters like L1-01 (protection selection) and L1-02 (overload time constant). Continuing to operate a motor in an OL1 condition severely risks damage to motor windings and insulation, leading to premature motor failure and costly downtime.

Vanlige årsaker

  • Motor rated current (Parameter L1-01) set incorrectly in the drive, below the actual motor nameplate Full Load Amps (FLA).
  • Mechanical overload on the motor shaft due to increased friction, binding, or a seized bearing in the driven equipment.
  • Drive acceleration/deceleration times (Parameters C1-01, C1-02) set too short for the load inertia, leading to excessive peak current during transients.
  • Supply voltage imbalance exceeding 2% at the drive input terminals (L1, L2, L3), causing higher current in one motor phase.
  • Motor cooling fan failure or obstructed cooling fins on the motor itself, leading to insufficient heat dissipation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Read the motor nameplate and verify that Parameter L1-01 (Motor Rated Current) in the drive matches the motor's Full Load Amps (FLA). Adjust if necessary.

  2. 2

    Measure the actual current (Amps) on all three motor phases using a clamp meter (e.g., Fluke 376 FC) during normal operation and compare to the value set in L1-01.

  3. 3

    Disconnect power and manually rotate the motor shaft and connected load. Verify smooth, free rotation without excessive resistance or binding.

  4. 4

    Using an insulation tester (e.g., Megger MIT420), perform a motor winding insulation resistance test from each phase to ground (500VDC for 1 minute).

  5. 5

    Monitor motor temperature directly with a thermal imager (e.g., FLIR T540) and compare to the motor's insulation class limits (e.g., Class F, 155°C).

  6. 6

    Verify supply voltage balance at the drive input terminals (L1, L2, L3) using a multimeter (e.g., Fluke 87V) and ensure phase voltages are within 2% of each other.

Se alle koder i denne manualen (63)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder