CE
MEMOBUS/Modbus Communication Error
Yaskawa · Drive Fault Codes
Hva betyr CE ?
A communication error has occurred on the MEMOBUS/Modbus network, preventing the drive from exchanging data correctly with a master controller or other devices. This can lead to loss of remote control, monitoring, or coordinated operation.
Vanlige årsaker
- Incorrect wiring or improper termination (e.g., missing or incorrect resistor values) on the MEMOBUS/Modbus network
- Incorrect communication parameters (e.g., slave address, baud rate, data format) in the drive (Parameters b2-01 to b2-04)
- Network interference or electrical noise affecting communication signals on the bus lines.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify wiring connections (e.g., A/B lines, shield) and bus termination resistors on the Modbus network.
- 2
Check drive parameters for Modbus communication (e.g., b2-01 Slave Address, b2-02 Baud Rate, b2-03 Data Format) and ensure they match the network configuration.
- 3
Monitor communication line signals using an oscilloscope to detect noise or signal integrity issues.