Brake chopper supervision

Vacon · NXS NXP

Hva betyr 12 ?

The brake chopper supervision has detected an issue, indicating either a missing or broken brake resistor, or a defective brake chopper unit. This fault prevents the drive from effectively dissipating regenerative energy, which can lead to overvoltage faults (Fault 2) during deceleration or when braking heavily.

Vanlige årsaker

  • Open circuit in the external braking resistor due to element failure or a broken connection.
  • Incorrectly wired braking resistor to the drive's R+/RB terminals, or loose connections.
  • Braking resistor sized incorrectly (resistance too high or too low) for the drive.
  • Defective internal brake chopper IGBT or its control circuit within the drive.
  • Short circuit across the braking resistor terminals or wiring, causing excessive current and protection trip.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Disconnect power to the drive and allow DC-link capacitors to discharge. Measure the resistance of the external braking resistor using a multimeter, verifying it matches the specified value (e.g., 50 Ohms).

  2. 2

    Inspect the wiring connections between the drive's R+/RB terminals and the braking resistor for loose terminals, corrosion, or damage.

  3. 3

    Check the brake chopper parameters (e.g., P6-11, P6-12) to ensure the brake resistor connection and values are correctly configured.

  4. 4

    Perform a diode test on the internal brake chopper IGBT (between DC+ and RB terminal) using a multimeter in diode mode, comparing readings against specifications.

  5. 5

    Verify that the braking resistor is properly mounted and has adequate ventilation to prevent overheating and premature failure.

Se alle koder i denne manualen (54)
Verifisert teknisk data. Sist oppdatert: March 2026