Oversetter...
9

Undervoltage

Vacon · NXP/C

Hva betyr 9 ?

The DC-link voltage has fallen below the voltage limits defined in Table 37. This is most likely caused by a low or interrupted supply voltage. Subcodes in T.14 (S1, S2, S3) can indicate if the DC-link was too low during run, no data was received from the power unit, or undervoltage control supervision tripped. A persistent undervoltage condition can prevent the drive from operating or restarting.

Vanlige årsaker

  • Input voltage below minimum threshold (e.g., P1-01 < P1-02).
  • Loss of one or more input phases.
  • Faulty main power supply unit.
  • Brownout condition affecting the DC bus voltage.
  • Incorrect voltage setting for the operating environment.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    If the fault occurred due to a temporary supply voltage break, reset the fault and restart the frequency converter.

  2. 2

    Measure the incoming AC supply voltage at the frequency converter's input terminals and verify it is stable and within the specified operating range (e.g., 380-480VAC for a 400V class drive).

  3. 3

    If the supply voltage is confirmed adequate, an internal failure has likely occurred. Contact your local distributor.

Se alle koder i denne manualen (11)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder