58
Mechanical Brake Status Mismatch
Vacon · NX Liquid-Cooled Drive
Hva betyr 58 ?
The actual physical status of the mechanical brake (e.g., engaged or disengaged) does not correspond to the control signal issued by the drive. This discrepancy suggests either a mechanical failure of the brake, an issue with its wiring, or a problem with the drive's brake control output.
Vanlige årsaker
- Actual mechanical brake status does not match the commanded status.
- Brake activation or deactivation signal failure.
- Brake status feedback sensor fault.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Physically inspect the mechanical brake to determine its actual engaged/disengaged state.
- 2
Verify the electrical connections and wiring between the drive's brake control output and the mechanical brake actuator.
- 3
Measure the voltage at the drive's brake control terminals to ensure the correct command signal is being sent.