50

Analogue Input Current Low

Vacon · NX Liquid-Cooled Drive

Hva betyr 50 ?

The current at the analogue input, which is configured for a 4 to 20mA signal range, has dropped below 4mA. This fault is commonly caused by a broken or loose control cable in the current loop or a failure of the signal source providing the analogue input.

Vanlige årsaker

  • Analogue input current reading is below the configured minimum (P0822).
  • Faulty current sensor or transducer.
  • Open circuit in the current input loop.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the entire current loop circuitry, including the analogue signal source, control cabling, and connections at the analogue input terminal, for breaks or loose wires.

  2. 2

    Measure the current output from the analogue signal source to confirm it is providing at least 4mA.