44

Device changed (different type)

Vacon · NX Liquid-Cooled Drive

Hva betyr 44 ?

An option board or power unit has been changed, and a new device of a different type or rating than the previous one has been detected. Subcodes S1-S5 specify the changed component: Control board, Control unit, Power board, Power unit, or Adapter board/slot.

Vanlige årsaker

  • Device type changed from expected (different model detected).
  • Incorrect device connected, not matching the programmed type.
  • Configuration mismatch for a new device type.
  • Device replacement with an incompatible model.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Reset the fault to acknowledge the change.

  2. 2

    If an option board was changed, reconfigure all relevant option board parameters according to the new device's specifications.

  3. 3

    If a power unit was changed, reconfigure all relevant AC drive parameters to match the new power unit's rating and type.