29
Thermistor fault
Vacon · NX Liquid-Cooled Drive
Hva betyr 29 ?
The thermistor input on the OPT-AF option board has detected an increase in the motor temperature. Subcode S1 indicates activation on the OPT-AF board, while S2 applies to special application contexts.
Vanlige årsaker
- Thermistor sensor disconnected or shorted.
- Thermistor value outside acceptable range (P1-18).
- Faulty thermistor component (e.g., on motor or heatsink).
- Wiring issue to the thermistor input.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check motor cooling system for obstructions or malfunctions to ensure adequate heat dissipation.
- 2
Verify motor loading is within specified limits for the motor and drive combination.
- 3
Inspect the thermistor connection to the OPT-AF board for proper wiring and continuity.
- 4
If the thermistor input of the option board is not in use, ensure it is properly short-circuited.
Verifisert teknisk data. Sist oppdatert: March 2026