Frequency converter over temperature

Vacon · 20 Compact

Hva betyr 14 ?

The frequency converter's heat sink is overheated, signifying insufficient cooling. Potential causes include blocked cooling airflow, high ambient temperature, accumulation of dust on the heatsink, or a switching frequency that is set too high in relation to the ambient conditions and motor load.

Vanlige årsaker

  • Overheating of the converter heatsink.
  • Ambient temperature too high.
  • Cooling fan failure or malfunction.
  • Blocked ventilation grilles or dust accumulation.
  • Excessive switching frequency or high load operation (P1-06).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify that the cooling air flow around the frequency converter is not obstructed.

  2. 2

    Check the ambient temperature around the drive and ensure it is within the specified operating limits.

  3. 3

    Clean any dust and debris from the heatsink fins to improve heat dissipation.

  4. 4

    Review the switching frequency setting and consider reducing it if it is excessively high for the current ambient temperature and motor load conditions.

Se alle koder i denne manualen (26)