Oversetter...
42
Brake resistor overtemperature
Vacon · 100 FLOW Application Guide
Hva betyr 42 ?
The brake resistor has exceeded its safe operating temperature limit. This indicates that the resistor is dissipating too much energy, possibly due to excessive braking, incorrect resistance value, or insufficient cooling.
Vanlige årsaker
- Brake resistor is undersized for the application's braking energy.
- Excessive regenerative energy being fed back into the drive.
- Faulty brake resistor element.
- Brake control parameters set incorrectly (e.g., P5-01, P5-02).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the resistance of the brake resistor using a multimeter.
- 2
Verify the brake resistor is properly connected to terminals BR1 and BR2.
- 3
Check the duty cycle of braking energy and compare with resistor specifications.
- 4
Monitor the voltage across the brake resistor terminals during deceleration.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Vacon 100 FLOW Application Guide