26

Startup Prevented

Vacon · 100 FLOW Application Guide

Hva betyr 26 ?

The drive cannot perform a startup because a new software (firmware or application), parameter setting, or other file affecting operation was loaded while a Run request was ON. The drive prevents startup to ensure configuration integrity and prevent improper operation.

Vanlige årsaker

  • A firmware update or parameter upload was performed while a run command (e.g., DI1 active, P0-10 = 1) was still present.
  • Application program was loaded or changed with the drive in a 'Ready' state, not 'Stopped' or 'Faulted'.
  • Changes to critical safety parameters or hardware configuration (e.g., option board change) were saved without cycling power.
  • Parameter setting download from an external tool (e.g., DriveWorks) occurred while the drive was expecting a run command.
  • Persistent run command signal (e.g., stuck digital input, communication bit) remained active during a configuration change.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Cycle the main input power to the drive (power off, wait for DC link discharge, power on).

  2. 2

    Ensure that any run command signals (e.g., digital input terminal 1 (DI1), communication command) are deactivated before attempting further configuration changes.

  3. 3

    Verify that no external control system is sending a persistent run command. Temporarily disconnect control wiring from terminals like DI1 to rule this out.

  4. 4

    Re-check the drive's run/stop source parameter (e.g., P0-10) to ensure it is correctly configured for the desired control method (e.g., HMI, DI, fieldbus).

  5. 5

    If a parameter file was recently uploaded, ensure the correct file version for the current application is active after cycling power.

Se alle koder i denne manualen (73)
Verifisert teknisk data. Sist oppdatert: March 2026