Brake chopper supervision

Vacon · 100 FLOW Application Guide

Hva betyr 12 ?

This fault indicates that either no brake resistor is installed, the installed brake resistor is broken, or there is a failure within the brake chopper unit itself. This prevents proper dissipation of regenerative energy.

Vanlige årsaker

  • The brake chopper circuit is not functioning as expected.
  • Excessive voltage detected across the brake chopper resistor.
  • Failure of the brake chopper semiconductor switch.
  • Brake resistor is open or shorted.
  • Brake chopper duty cycle exceeded.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the brake resistor for continuity and proper resistance value.

  2. 2

    Verify the cabling between the frequency converter and the brake resistor for proper connection and integrity.

  3. 3

    If the resistor and cabling are confirmed good, the chopper unit is faulty.

Se alle koder i denne manualen (73)
Verifisert teknisk data. Sist oppdatert: March 2026