113

Pump Running Time Limit Exceeded

Vacon · 100 FLOW Application Guide

Hva betyr 113 ?

In a Multipump system, one or more pump running time counters have exceeded a user-specified alarm or fault limit. This indicates that a pump has reached its programmed maintenance interval or has been operating for an excessively long period without intervention. Timely maintenance prevents wear and premature failure.

Vanlige årsaker

  • Maintenance interval parameter (e.g., P7-10 for run time limit) set too low for the actual pump operating schedule or expected service life.
  • Incorrect sequencing logic or pump rotation strategy causing one pump to accumulate significantly more run hours than others in a multi-pump system.
  • Failure to reset the pump run-time counter (e.g., P7-11) after scheduled maintenance, leading to premature limit triggering.
  • Increased demand on a specific pump due to operational changes or system imbalances, resulting in it running more frequently or longer.
  • Fault in the pump's control circuit causing it to run continuously or more often than commanded, accumulating excessive hours.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Retrieve the current run-time counter value for the affected pump (e.g., P7-11) and compare it to the set limit (e.g., P7-10).

  2. 2

    2. Review the pump sequencing parameters and rotation strategy (e.g., P7-05, P7-06) to ensure balanced operation across all pumps.

  3. 3

    3. Evaluate if the run-time limit parameter (e.g., P7-10) is appropriate for the pump type, application, and planned maintenance schedule.

  4. 4

    4. If maintenance has been performed, manually reset the pump's run-time counter (e.g., P7-11 set to 0) as per the system's maintenance procedure.

  5. 5

    5. Monitor the pump's operational status and command signals (e.g., digital output to contactor) to verify it is running only when required by the system.

Se alle koder i denne manualen (73)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Vacon 100 FLOW Application Guide