Oversetter...
230672

SI CU: Control Unit software incompatible

Siemens · SINUMERIK 828D

Hva betyr 230672 ?

The existing Control Unit software does not support the safe drive-based motion monitoring function, leading to a STOP A that cannot be acknowledged. The fault value (r0949) is typically for internal Siemens troubleshooting. This indicates a fundamental incompatibility between the CU's software version and the attempted safety function.

Vanlige årsaker

  • The installed Control Unit firmware version is older and does not include the necessary Safety Integrated (SI) functionalities for drive-based motion monitoring.
  • Firmware update was incomplete or corrupted, resulting in a partially updated or incompatible software state on the Control Unit.
  • Incorrect Control Unit type selected during hardware configuration (e.g., using a non-SI capable CU with a safety application).
  • Parameterization error attempting to enable SI motion monitoring functions (e.g., SS1, SLS, SLP) on a Control Unit that fundamentally lacks support.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Verify the exact part number and firmware version of the installed Control Unit, comparing it against the system requirements for safe drive-based motion monitoring.

  2. 2

    2. Update the Control Unit firmware to a version that explicitly supports the required Safety Integrated motion monitoring functions (e.g., via TIA Portal or STARTER).

  3. 3

    3. Perform a full factory reset (e.g., P0010=30, P0970=1) of the Control Unit after firmware update, then re-commission all parameters and safety settings.

  4. 4

    4. Check the hardware configuration in the engineering software (e.g., TIA Portal) to ensure the correct Control Unit type (e.g., specific SINAMICS CU model with SI) is selected.

  5. 5

    5. Review the Safety Integrated commissioning documentation for the specific Control Unit to confirm its capabilities and configuration requirements.

Se alle koder i denne manualen (37)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder