Oversetter...
A07852

External alarm 3

Siemens · DCM

Hva betyr A07852 ?

The BICO signal for 'external alarm 3' was triggered, indicating that the predefined condition for this alarm has been met. This is a user-configurable alarm tied to an external event, sensor, or logic input. The specific cause is defined by parameter p2117.

Vanlige årsaker

  • Input signal connected to parameter P2102 (External alarm 3 trigger) transitioned from 0 to 1, indicating a tripped safety interlock or sensor.
  • A process limit switch (e.g., high-level sensor, over-pressure switch) wired to a digital input, which is mapped to P2102.
  • A PLC output controlling an external warning condition, mapped to the drive's digital input and subsequently linked via BICO to P2102.
  • An over-temperature switch on an external motor or bearing, wired to the drive's digital input to trigger the alarm.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Identify the digital input (e.g., DI0, DI1) that is BICO-connected to parameter P2102 (External alarm 3 trigger).

  2. 2

    2. Monitor the status of the identified digital input using parameter r0722[x] (e.g., r0722[0] for DI0) to verify its current state.

  3. 3

    3. Trace the physical wiring from the identified digital input back to its source (e.g., limit switch, sensor, PLC output).

  4. 4

    4. Inspect the external sensor or switch for its activated state; for example, check if a pressure switch has exceeded its setpoint.

  5. 5

    5. Verify the logic and configuration of the external device causing the alarm, ensuring its operating limits are appropriate for the application.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder