External alarm 1
Siemens · DCM
Hva betyr A07850 ?
The BICO signal for 'external alarm 1' was triggered, indicating that the predefined condition for this alarm has been met. This is a user-configurable alarm tied to an external event, sensor, or logic input. The specific cause is defined by parameter p2112.
Vanlige årsaker
- Input signal connected to parameter P2100 (External alarm 1 trigger) transitioned from 0 to 1, indicating a tripped safety interlock or sensor.
- A process limit switch (e.g., high-level sensor, over-pressure switch) wired to a digital input, which is mapped to P2100.
- A PLC output controlling an external warning condition, mapped to the drive's digital input and subsequently linked via BICO to P2100.
- An over-temperature switch on an external motor or bearing, wired to the drive's digital input to trigger the alarm.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Identify the digital input (e.g., DI0, DI1) that is BICO-connected to parameter P2100 (External alarm 1 trigger).
- 2
2. Monitor the status of the identified digital input using parameter r0722[x] (e.g., r0722[0] for DI0) to verify its current state.
- 3
3. Trace the physical wiring from the identified digital input back to its source (e.g., limit switch, sensor, PLC output).
- 4
4. Inspect the external sensor or switch for its activated state; for example, check if a pressure switch has exceeded its setpoint.
- 5
5. Verify the logic and configuration of the external device causing the alarm, ensuring its operating limits are appropriate for the application.