Oversetter...
15
24 V supply
SEW Eurodrive · MOVIFIT-FC Inverter
Hva betyr 15 ?
The supply voltages 24V_C and/or 24V_P are too low, falling below the required operating threshold for the unit's electronics. This inadequate voltage supply can lead to unpredictable behavior or complete unit shutdown.
Vanlige årsaker
- Low or unstable 24 VDC auxiliary supply voltage.
- Faulty external 24 VDC power source.
- Wiring issue with the 24 VDC input.
- Internal 24 VDC power regulation failure.
- Parameter P0007 (24V fault reaction) settings.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the 24 V supply voltages 24V_C and/or 24V_P to ensure they are within the permissible range (24 V ± 25% with residual ripple max. 13% per EN 61131-2).
- 2
Reset the fault by switching off the DC 24 V supply voltage.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: SEW Eurodrive MOVIFIT-FC Inverter