F109-56

Plausibility fault in encoder interface (A3401 = encoder 1 and A3402 = encoder 2)

SEW Eurodrive · MOVIDRIVE MDX60B/61B Variable Speed Drive

Hva betyr F109-56 ?

The encoder interface (A3401 or A3402) does not match the configured data. This suggests a mismatch between the physical encoder type/connection and the drive's settings.

Vanlige årsaker

  • Encoder data plausibility check failed for encoder 1 (A3401) or encoder 2 (A3402).
  • Position or velocity feedback is inconsistent.
  • Encoder resolution mismatch or incorrect setup.
  • Mechanical issue causing inconsistent encoder output.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check encoder type and configuration (SSI/incremental).

  2. 2

    Check the encoder connection/wiring.

  3. 3

    Check the polarity of the encoder data.

  4. 4

    Check function of the encoder.

Se alle koder i denne manualen (60)