Internal error
SEW Eurodrive · Drives
Hva betyr 38 ?
An unspecified internal error has occurred within the MOVIMOT® inverter. This type of error usually requires specialized diagnostic tools and expertise.
Vanlige årsaker
- Unspecified internal system malfunction.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify input supply voltage (L1, L2, L3) at the MOVIMOT® inverter's main power terminals against the rated nominal voltage.
- 2
Inspect the motor cable for any visible damage, chafing, or signs of stress, and check all motor connections (U, V, W, PE) for tightness and proper termination.
- 3
Check all operational and motor-specific parameter settings within the MOVIMOT® inverter using SEW diagnostic software (e.g., MOVITOOLS® MotionStudio) for correctness and compare with the last known good configuration.
- 4
Measure the insulation resistance of the motor windings to ground and phase-to-phase with the MOVIMOT® inverter disconnected, ensuring it meets manufacturer specifications.
- 5
Perform a complete power cycle of the MOVIMOT® inverter by disconnecting and reconnecting the main power supply, then monitor for fault reoccurrence.