0C8A
Error in outgoing MFI interface (OUT1)
SEW Eurodrive · Drives
Hva betyr 0C8A ?
The outgoing MFI interface (OUT1) was activated even though no station is connected or was configured in the master. This indicates a mismatch between the physical setup and the INTERBUS master configuration.
Vanlige årsaker
- No station physically connected to the outgoing interface OUT1.
- Outgoing interface OUT1 not configured in the INTERBUS master.
- Incorrect setting of DIP switch 6 (NEXT/END) on the MFI.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the setting of DIP switch 6 (NEXT/END) on the MFI. If the MFI is the last station in the bus segment, this switch must be set to END.
- 2
Verify that a station is physically connected to OUT1 if it is enabled.
- 3
Check the INTERBUS master configuration to ensure OUT1 is correctly configured for connected stations.
Verifisert teknisk data. Sist oppdatert: March 2026