This fault occurs when the motor cannot be supplied with the correct amount of current during the pre-magnetizing time, particularly in hoist applications. This indicates an impedance mismatch or inadequate current capacity, preventing proper motor startup.
Vanlige årsaker
- Rated motor power is too small in relation to the rated inverter power.
- Motor cable cross-section is too small.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the connection between the MOVIMOT inverter and the motor, verifying cable cross-section.
- 2
Verify that the rated motor power is appropriately matched with the rated inverter power.
- 3
Reset the fault by switching off and then switching on the DC 24V supply voltage.
- 4
Reset the error via the error reset function.