AI L1 Under Voltage
Schneider Electric · XW Pro NA Operation Guide
Hva betyr F34 ?
This fault indicates an L1 under-voltage condition (108 V) detected by the anti-islanding protection, triggering a slow disconnect. This mechanism ensures the inverter disconnects from an unstable grid, protecting both the inverter and grid from potential damage due to insufficient voltage.
Vanlige årsaker
- Grid L1-Neutral voltage dropping below 108 V for a sustained period, indicating persistent grid brownout or heavy load drawing power from phase L1.
- Undersized utility grid connection or long feeder cables causing significant voltage drop on phase L1 under normal operating loads.
- Inverter's L1 voltage sensing circuit experiencing a degradation in accuracy or intermittent measurement loss over time.
- Anti-islanding parameter P_AI_L1_Volt_Min_Slow set too high, triggering disconnects on minor, acceptable voltage dips.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Using a true RMS multimeter, continuously monitor the L1-Neutral voltage at the inverter's AC input terminal L1 over several hours to detect persistent low voltage.
- 2
Compare the sustained L1-Neutral voltage readings against the specified 108 V trip threshold and the inverter's P_AI_L1_Volt_Min_Slow parameter.
- 3
Verify the tightness and condition of the L1 phase and neutral conductor connections at the inverter's input terminals (e.g., Terminal L1, Terminal N).
- 4
Investigate the local grid connection for other large loads drawing power from phase L1 that might cause voltage sags, especially during startup.
- 5
If external voltage is stable, verify the inverter's internal L1 voltage measurement offset parameter (e.g., P_AI_L1_Volt_Offset) for potential misconfiguration.