F23

AI Over Frequency

Schneider Electric · XW Pro NA Operation Guide

Hva betyr F23 ?

This Automatic Fault occurs due to an over-frequency anti-islanding condition, detected when the AC frequency exceeds qualification limits. The inverter stops selling power and disconnects from the grid to ensure safety and regulatory compliance.

Vanlige årsaker

  • Utility grid frequency exceeding the configured upper limit (e.g., 60.5 Hz for a 60 Hz system) for anti-islanding detection.
  • Inverter's internal frequency measurement circuit drift or calibration error.
  • Nearby generator or grid disturbance causing transient frequency spikes.
  • Misconfiguration of anti-islanding parameters (e.g., Parameter P4-05 for over-frequency threshold set too tight).
  • Inverter attempting to operate in an unintentional islanded mode with a local load, leading to frequency instability.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure utility grid frequency at the inverter's AC input terminals (L1, L2, L3) using a power quality analyzer to verify grid stability.

  2. 2

    Verify anti-islanding frequency thresholds configured in the inverter (e.g., Parameter P4-05, P4-06) against local utility requirements.

  3. 3

    Check all external grid connection points and switchgear for loose connections or arcing that could generate electrical noise affecting frequency measurement.

  4. 4

    Perform an inverter self-test or calibration routine if available, to verify the accuracy of its internal frequency measurement circuit.

  5. 5

    Temporarily disable anti-islanding protection (if allowed by local regulations and safe to do so for testing) to determine if the fault clears.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026