FCF2
Output Contactor Open
Schneider Electric · Altivar Machine ATV320 Variable Speed Drive
Hva betyr FCF2 ?
Indicates that the output contactor is detected as open when it should be closed. This prevents the drive from supplying power to the motor, resulting in a failure to start or operate. This could be due to a wiring issue, contactor fault, or an active interlock.
Vanlige årsaker
- The output contactor fails to close when commanded.
- Insufficient voltage or current to energize the contactor coil.
- Mechanical obstruction preventing the contactor from engaging.
- Faulty control signal (e.g., from P2-10) commanding the contactor to close.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify control wiring to the output contactor coil for continuity and correct voltage.
- 2
Check the output contactor for mechanical damage, an open coil circuit, or burnt contacts.
- 3
Ensure all safety interlocks or permissive conditions for contactor closure are met.
- 4
Measure the voltage supplied to the contactor coil when it should be energized.