USF

Undervoltage

Schneider Electric · ALTIVAR 28 Variable Speed Drive

Hva betyr USF ?

This fault indicates that the input voltage supplied to the drive controller is too low, possibly due to a transient voltage dip, a persistent low line voltage, or a damaged internal component like a load resistor. Undervoltage can cause erratic drive behavior, loss of motor control, and potential component stress.

Vanlige årsaker

  • Incoming AC line voltage consistently below the drive's minimum rated input voltage (e.g., below 340V for a 400V drive).
  • Transient voltage sag or brownout on the incoming AC power supply.
  • Loose or corroded connections at the drive's input terminals (L1, L2, L3) or upstream power distribution.
  • Blown input fuse on one or more phases leading to phase imbalance and low DC bus.
  • Damage to the drive's internal rectifier bridge causing insufficient DC bus charging.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Measure incoming AC line voltage (L1-L2, L2-L3, L3-L1 terminals) with a true RMS multimeter and compare to drive's minimum rated input voltage.

  2. 2

    2. Inspect all input power connections (L1, L2, L3) for tightness and signs of corrosion.

  3. 3

    3. Check continuity of all incoming line fuses (if present) and replace any blown fuses.

  4. 4

    4. Monitor DC bus voltage (drive display parameter P0-08 or similar) during operation to observe voltage dips.

  5. 5

    5. Confirm the mains transformer (if used) is correctly sized for the load and has adequate voltage regulation.

Se alle koder i denne manualen (13)
Verifisert teknisk data. Sist oppdatert: March 2026