F001

Precharge

Schindler · Easy Altivar ATV310 Drive

Hva betyr F001 ?

For the ATV310 drive, this fault indicates an issue within the internal DC bus precharge circuit. This typically involves a fault with the charging relay control or damage to the precharge resistor, preventing the DC bus capacitors from charging correctly upon power-up.

Vanlige årsaker

  • Charging relay control fault within the drive's precharge circuit
  • Charging resistor damaged or failed in the precharge circuit
  • Instability or transient issues with the main input supply voltage

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Turn the ATV310 drive off completely, wait for the display to extinguish, and then turn it back on.

  2. 2

    Check the main power input connections to the drive for tightness and correct phase sequencing.

  3. 3

    Verify the stability of the main input supply voltage, checking for sags or swells during power-up.