UP1
Undervoltage
Schindler · Altivar 212 Variable Frequency Drive
Hva betyr UP1 ?
This fault indicates that the input voltage to the Altivar 212 drive is too low, potentially causing instability or improper operation. This can lead to a drive trip to prevent damage.
Vanlige årsaker
- The input voltage to the drive is too low.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the input voltage at the drive terminals (R/L1, S/L2, T/L3) and rectify the supply trouble.
- 2
Select the correct setting for parameter F627 ([Undervolt detect.]).
- 3
Enable catch on the fly function (F301).
- 4
Set parameter F302 ([Supply loss behav.]) to 2 (Freewheel).
Verifisert teknisk data. Sist oppdatert: March 2026