OCA
Short Circuit Inverter at Start
Schindler · Altivar 212 Variable Frequency Drive
Hva betyr OCA ?
This fault indicates a short circuit condition detected within the Altivar 212 drive's output inverter stage during motor startup, usually caused by a ground fault.
Vanlige årsaker
- Ground fault in the inverter output or motor/cables.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Use a 1000 V testing tool (megger) to check the motor windings for insulation resistance to ground.
- 2
Use a 1000 V testing tool (megger) to check the motor cables for insulation resistance to ground.