OC1

Overcurrent During Acceleration

Schindler · Altivar 212 Variable Frequency Drive

Hva betyr OC1 ?

This fault indicates an overcurrent condition during motor acceleration by the Altivar 212 drive, often caused by excessively short acceleration times, incorrect motor control settings, or high-inertia loads.

Vanlige årsaker

  • Acceleration time is too short (ACC or F500).
  • Incorrect setting of [Mot cont. mode sel.] (Pt).
  • Drive is starting into a rotating load.
  • Drive is powering a low impedance motor.
  • Ground fault in the motor or cables.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Increase the acceleration time parameters (ACC or F500).

  2. 2

    Select the correct setting for parameter [Mot cont. mode sel.] (Pt).

  3. 3

    Enable catch on the fly function (F301).

  4. 4

    Adjust the switching frequency parameter F300.

  5. 5

    Set parameter F316 ([Switch. freq. mode]) to 1 or 3.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026