Fd2
Closed Damper 2 Fault
Schindler · Altivar 212 Variable Frequency Drive
Hva betyr Fd2 ?
This fault indicates that the damper is blocked open or soldered, preventing it from closing. This condition can affect temperature control or system operation by not restricting airflow as intended.
Vanlige årsaker
- Damper is blocked open or soldered.
- Incorrect settings for damper feedback or relay control (F130, F132, F580).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Set parameter [Damper fdb type] (F580) to 0 (No feedback) or 1 (LI L set).
- 2
Check the FL relay connection (FLA/FLB terminals) for proper wiring.
- 3
Verify the relay configuration using parameters F130 ([RY Relay Function 1]) and F132 ([FL Relay Function]).