Fd1

Closed Damper 1 Fault

Schindler · Altivar 212 Variable Frequency Drive

Hva betyr Fd1 ?

This fault indicates that the damper is locked in a closed position, preventing proper air flow or ventilation, which can lead to overheating or process issues. The drive typically locks in this fault mode.

Vanlige årsaker

  • Damper is locked in closed position.
  • Incorrect settings for damper feedback or relay control (F130, F132, F583).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Set parameter [Damper flt behavior] (F583) to 0 (No fault).

  2. 2

    Check the FL relay connection (FLA/FLB terminals) for proper wiring.

  3. 3

    Verify the relay configuration using parameters F130 ([RY Relay Function 1]) and F132 ([FL Relay Function]).