EF2

Ground Fault

Schindler · Altivar 212 Variable Frequency Drive

Hva betyr EF2 ?

This fault signals a ground fault in the motor or the motor cables, indicating an insulation breakdown or improper grounding in the output circuit of the Altivar 212 drive.

Vanlige årsaker

  • Ground fault in the motor windings.
  • Ground fault in the motor cables.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure insulation resistance between motor phases and ground using a megger.

  2. 2

    Measure insulation resistance between motor cables and ground using a megger.

  3. 3

    Inspect motor and motor cables for physical damage or wear causing a ground path.

Se alle koder i denne manualen (60)